Activities / Fire suppression / Free tool

FM-200 Calculator: Agent Quantity and Cylinders

Calculate the FM-200 (HFC-227ea) quantity for a server room, electrical room or archive, with the raised floor and ceiling void calculated separately, plus cylinder size, approximate number of nozzles and a safety check for occupied spaces.

FM-200 suppression system: wall-mounted cylinders with manifold, piping and nozzles

Room data

Advanced settings

Estimated result

0kg FM-200
-Cylinders (25 bar)
-Fill density (kg/L)
-Approx. nozzles
ZoneVolume m³Agent kgNozzles

Calculation details

NFPA 2001 equation: W = (V ÷ S) × C ÷ (100 − C) × altitude factor, where S = 0.1269 + 0.000513 × T is the specific vapour volume at the minimum room temperature. 25 bar cylinders filled between 0.5 and 1.0 kg/L. Nozzle count is approximate, based on a 360° nozzle covering a square of up to 12.3 m and up to 4.87 m height per level; the final number and positions come from the listed hydraulic flow calculation.

Request an approved design and quotation

Your calculation is sent with the request, and we reply with the design, hydraulic calculation and price.

Comparison with other agents for the same room

The same volume and hazard calculated with other agents. For details use the Gas Suppression Calculator.

AgentConcentrationQuantityCylindersSuitable for occupied spaces

FM-200 frequently asked questions

What is FM-200?

FM-200 is the common name for HFC-227ea, a clean extinguishing agent stored as a liquid in nitrogen-pressurised cylinders. It discharges within 10 seconds, fills the room and puts out the fire without water or powder and without leaving residue on equipment, which is why it is used in server, telecom, electrical and archive rooms.

Is FM-200 safe for people?

Yes, at normal design concentrations (6.25% to 9%); the no-observed-adverse-effect level (NOAEL) is 9%, so the calculator checks the concentration at the maximum room temperature. Systems are still designed with a pre-discharge alarm and a 30-second delay so occupants can leave.

Why are the raised floor and ceiling void calculated separately?

Each enclosed void must reach the design concentration, so its volume, agent and nozzles are calculated on their own and the quantities are then added into the same cylinders. Ignoring the raised floor is one of the most common mistakes, because the cables under it are a main fire source.

How much FM-200 does a small server room need?

As a rough rule about 0.55 to 0.6 kg per cubic metre at 20 °C. A 5 × 4 × 3 m room needs about 33 kg, more with a raised floor or ceiling void. Use the calculator above for your room.

Is the calculator result enough for installation?

No. The result is an estimate for planning and budgeting. An approved design needs a site visit, a room integrity check and a hydraulic calculation of pipe sizes and nozzle orifices with the listed (UL/FM) flow software.